Size Electrical Wire Calculator
Recommended conductor
8 AWG
Wire Size & Gauge Calculator
Recommended conductor area
16,510 cmil
Required ampacity
40.00 A
Table 310.16 ampacity
55 A
Ambient correction factor
1.0000
Conductor-count adjustment factor
1.000
Corrected ampacity
55.000 A
Usable ampacity after termination limits
50.000 A
Voltage drop at the recommended size
2.604 %
Size needed for the voltage-drop limit
8 AWG
Equipment grounding conductor
10 AWG
Worked out from NFPA 70, National Electrical Code — Table 310.16, Allowable Ampacities of Insulated Conductors and 4 other sources.
Reference data is transcribed from the 2023 NFPA 70 tables. Confirm the values against the edition your authority having jurisdiction has adopted.
The equipment grounding conductor shown is read from the required ampacity as a stand-in for the overcurrent device rating; size it from the device actually installed, and increase it proportionally under 250.122(B) when the phase conductors are upsized for voltage drop.
Advisory only. Conductor selection depends on the NFPA 70 edition adopted by your authority having jurisdiction, the wiring method, termination listings, conduit fill, fault duty and load classification. A licensed electrical professional must approve any installed design.
How this is worked out
5 steps
- Required ampacity = 40 A.
- Smallest copper conductor whose corrected ampacity reaches 40 A: 8 AWG (55 A at 90 degC x 1.0000 ambient x 1 bundling = 55.00 A, held to 50.00 A by the terminations).
- Voltage drop at 8 AWG over 100 ft: 2.604 % against a 3 % allowance.
- Ampacity governs; the voltage-drop allowance is already satisfied at this size.
- Equipment grounding conductor for a 40 A device (NEC Table 250.122): 10 AWG.