Size Electrical Wire Calculator

Wire Size & Gauge Calculator works out Recommended conductor and Recommended conductor area from What to calculate, Load current and Continuous load (3 hours or more). The default figures on this page give recommended conductor of 8 AWG; change any entry and the result, the working and the sources update together.

Recommended conductor
8 AWG
Wire Size & Gauge Calculator
Recommended conductor area
16,510 cmil
Required ampacity
40.00 A
Table 310.16 ampacity
55 A
Ambient correction factor
1.0000
Conductor-count adjustment factor
1.000
Corrected ampacity
55.000 A
Usable ampacity after termination limits
50.000 A
Voltage drop at the recommended size
2.604 %
Size needed for the voltage-drop limit
8 AWG
Equipment grounding conductor
10 AWG
Worked out from NFPA 70, National Electrical Code — Table 310.16, Allowable Ampacities of Insulated Conductors and 4 other sources.
Reference data is transcribed from the 2023 NFPA 70 tables. Confirm the values against the edition your authority having jurisdiction has adopted.
The equipment grounding conductor shown is read from the required ampacity as a stand-in for the overcurrent device rating; size it from the device actually installed, and increase it proportionally under 250.122(B) when the phase conductors are upsized for voltage drop.
Advisory only. Conductor selection depends on the NFPA 70 edition adopted by your authority having jurisdiction, the wiring method, termination listings, conduit fill, fault duty and load classification. A licensed electrical professional must approve any installed design.

Your figures

Updates as you type
The continuous plus non-continuous load the conductor must carry.
Used by the ampacity and derating modes.
NEC 110.14(C): the ampacity used for sizing may not exceed the Table 310.16 value at the lowest-rated termination.
Used by the equipment grounding conductor mode (NEC Table 250.122).
Sheet steel gauge runs 3 to 38; AWG runs 4/0 (entered as -3) to 38.

How this is worked out

5 steps
  1. Required ampacity = 40 A.
  2. Smallest copper conductor whose corrected ampacity reaches 40 A: 8 AWG (55 A at 90 degC x 1.0000 ambient x 1 bundling = 55.00 A, held to 50.00 A by the terminations).
  3. Voltage drop at 8 AWG over 100 ft: 2.604 % against a 3 % allowance.
  4. Ampacity governs; the voltage-drop allowance is already satisfied at this size.
  5. Equipment grounding conductor for a 40 A device (NEC Table 250.122): 10 AWG.

Its 5 worked examples are re-run on every release, last on 15 September 2026. What changed

Sources and references

5 sources
NFPA 70, National Electrical Code — Table 310.16, Allowable Ampacities of Insulated Conductors
2023 · Ampacities at 60/75/90 degC for copper and aluminium, based on 30 degC ambient and not more than three current-carrying conductors.
ASTM B258, Standard Specification for Nominal Diameters and Cross-Sectional Areas of AWG Sizes
Defines the American Wire Gauge geometric series d = 0.005 x 92^((36 - n)/39) inches.
Manufacturers' Standard Gauge for Sheet Steel
Gauge is defined by weight; sheet steel weighs 41.82 lb per square foot per inch of thickness, so thickness = (lb/sq ft) / 41.82. Gauge 3 is 10 lb/sq ft = 0.2391 in.

What the Wire Size & Gauge Calculator calculates

Sizes copper or aluminium conductors from load current, run length and voltage-drop allowance, derates ampacity for ambient temperature and bundling, looks up equipment grounding conductors, and converts sheet-metal gauge numbers to thickness.

How to use this Wire Size & Gauge Calculator

Enter What to calculate, Load current, Continuous load (3 hours or more) and Conductor material. Recommended conductor updates as you type, and “Use a worked example” loads checked figures you can adjust. Change one figure at a time to see what drives the result.

How the result is worked out

Open “How this is worked out” beside the result for the step-by-step calculation behind Recommended conductor, Recommended conductor area and Required ampacity.

The method follows NFPA 70, National Electrical Code — Table 310.16, Allowable Ampacities of Insulated Conductors, NFPA 70 — 310.15(B)(2) ambient correction, Table 310.15(C)(1) adjustment, 110.14(C) termination ratings, 240.4(D) small-conductor limits, 210.19(A)/215.2(A)(2) voltage-drop informational notes, NFPA 70 — Table 250.122, Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment, ASTM B258, Standard Specification for Nominal Diameters and Cross-Sectional Areas of AWG Sizes and Manufacturers' Standard Gauge for Sheet Steel.

100 A feeder, copper, 100 ft at 240 V example

With What to calculate: wire-size, Load current: 100, Continuous load (3 hours or more): false, Conductor material: copper, the calculator returns Required ampacity: 100, Recommended conductor: 3 AWG, Voltage drop at the recommended size: 2.04294945. This example is checked against an independent source in the test suite.

What you can compare

Change one input at a time to see how it affects Recommended conductor, Recommended conductor area and Required ampacity. The inputs you can vary are What to calculate, Load current, Continuous load (3 hours or more), Conductor material, Conductor size and Conductor insulation rating.

Understanding Recommended conductor, Recommended conductor area and Required ampacity

Advisory only. Conductor selection depends on the NFPA 70 edition adopted by your authority having jurisdiction, the wiring method, termination listings, conduit fill, fault duty and load classification. A licensed electrical professional must approve any installed design.

Results are general information, not financial, tax, legal, medical or engineering advice. Check any decision that matters with a qualified professional.

Embed this calculator on your website

Copy this code into any page. The calculator appears with the figures currently entered, sizes itself to fit, and a small credit line links back here. Free, no account, no ads inside it, no tracking of your readers. Set your own figures and fixed fields; Personal removes the credit line, sets your colour and shows you which sites use it.

Preview

See something wrong? Report a problem with this calculator

Frequently asked questions

What information do I need for the Wire Size & Gauge Calculator?

You need What to calculate, Load current, Continuous load (3 hours or more), Conductor material, Conductor size, Conductor insulation rating, Termination temperature rating and Ambient temperature. The page opens with default figures that give recommended conductor of 8 AWG, so you can see the scale before entering your own.

What does this Wire Size & Gauge Calculator show?

It shows Recommended conductor, Recommended conductor area, Required ampacity, Table 310.16 ampacity, Ambient correction factor, Conductor-count adjustment factor, Corrected ampacity and Usable ampacity after termination limits, with the working and any warnings for your entries.

Can I check how the Wire Size & Gauge Calculator result was calculated?

Yes. The “How this is worked out” section shows the calculation steps, and the sources section identifies the references used for the method.